"World's recognized authority in power treatment"

EON Model EL3 (10kW to 33kW) Three Phase



Description

Meeting stringent design and performance specifications, the self-diagnostic, self-testing EON Model EL3 centralized emergency lighting inverter is UL 924 listed as “Emergency Lighting Equipment” and “Auxiliary Lighting and Power Equipment”, as well as NFPA compliant as “Life Safety Equipment”. The EON meets NFPA 101, NFPA 111, NEC and IBC requirements, and provides the industry’s most advanced life safety system testing available!

Key EON options include output distribution with either monitored or unmonitored circuit breakers, normally off bus for standby (normally off) emergency light fixtures, and remote communications via BACnet, Ethernet, MODBUS TCP, or MODBUS RS485.

The EON features one of the smallest three phase cabinet footprints in the industry! See how our 90 minute Inverter cabinet footprint compares to others!

Available in 10kW to 33kW three phase sizes, the EON is the ideal emergency power solution for facilities where safe egress and life safety are imperative.

Three Phase Sizes: 10kW, 13kW, 14kW, 15kW, 16kW, 17kW, 20kW, 22kW, 24kW, 26kW, 28kW, 30kW, 32kW, and 33kW



Features & Benefits
Technical Specs
Applications
FAQ



General Specifications


Guide Specifications


Back to top Top
Features & Benefits

  • Full compliance with NFPA 101 – computer-based, self-testing / self-diagnostic emergency lighting system with data-logging
  • Compact footprint – “front access” cabinet is physically smaller than competitors’ three phase emergency lighting inverter products, without compromising performance or serviceability
  • Reliability, plus compatibility – provides reliable, regulated voltage during normal and emergency power modes; compatible with all lighting fixture types, including LED
  • Easy installation and low cost-of-ownership – requires only (1) battery cabinet for 90 minutes runtime, and only batteries with front-access terminals are used
  • Automatic static bypass on overload or system failure
  • Integral internal bypass includes a make-before-break switch with a secure push-to-turn function – provides an uninterrupted bypass of the inverter system
  • Intellistat TS™ monitor – provides quick full-access to all inverter features, allows all programming to be done directly from touchscreen display, and provides system diagnostics and testing
  • Optional normally off bus – provides standby power to “normally off” emergency lights when utility power is lost or is inadequate
  • Optional front-access, side-mounted output distribution cabinet – includes 12 pole positions per phase to accommodate 1, 2, and 3 pole circuit breakers; see FAQ’s for additional details
  • Optional NetMinder™ communications – provides remote monitoring of inverter status, test results, alarms, and electrical measurements via BACnet, Ethernet, MODBUS TCP, or MODBUS RS485


Back to top Top
Technical Specs

  • Input and Output Nominal Voltage: 208/120V, 480/277V, or 600/347V Wye
  • Input Operating Voltage Range: +10%, -15% at full load
  • Input Frequency: 60 Hz, ± 2.5% (50 Hz models available)
  • Input Power Factor Correction: > .98 pF typical, at full load
  • Output Voltage Regulation: ± 3% from nominal, typical
  • Output Frequency: ± 0.5% while in battery operation mode
  • Output Voltage Distortion: Typically 3% output THD with linear load
  • Overload: 110% for 2 minutes, 125% for 30 seconds, 150% for 10 seconds (without use of static bypass)
  • Efficiency: 90% typical
  • Operating Temperature: 20º to 35º C (for UL 924 Listed models) – UL testing performed at 40º C under full load and at low line input voltage. Optimum battery performance and life at 25º C
  • Operating Temperature: 10º to 40º C (for models C-UL Listed to CSA C22.2 No. 141-10). Optimum battery performance and life at 25º C
  • Battery Time: UL 924 Listed 90 minutes at full-rated kW output, or with optional run times from 15 minutes to 4 hours. C-UL Listed to CSA C22.2 No. 141-10 with 30 minutes run time


Back to top Top
Applications

  • Theaters / Concert Halls
  • Auditoriums
  • Worship Facilities
  • Conference / Banquet Centers
  • Shopping Malls
  • Casinos
  • Sports Facilities
  • University Buildings
  • Healthcare Facilities
  • Correctional Facilities
  • Subway / Train Stations
  • Industrial Manufacturing
  • Warehouses



  • What are centralized lighting inverters and why use them?

  • A centralized lighting inverter is an electronic system that converts DC battery power to standard AC voltages to provide back-up for lighting systems during a power outage. Centralized lighting inverters provide a single point source of power for all emergency lighting and exit signs. This provides for a controlled logical wiring scheme and results in a single point for monthly and annual testing.



  • Is the EON Model EL3 NFPA 101 compliant?

  • YES! The EON is UL 924 listed under Emergency Lighting and Power Equipment, in accordance with the ANSI/NFPA 101 “Life Safety Code”, Article 700 of ANSI/NFPA 70, “National Electric Code”, and the “International Building Code” (IBC).



  • Does the EON Model EL3 automatically perform testing according to NFPA 101?

  • YES! The EON meets the NFPA 101 definition of a computer-based, self-testing / self-diagnostic emergency lighting system with data-logging (NFPA 7.9.3.1.3). Both periodic and annual tests are performed automatically, and the results are logged with a date and time stamp. Both alarm and test logs provide a history of events, and the ability to generate an NFPA-compliant report.



  • How is the EON Model EL3 different from other lighting inverters with automatic testing?

  • BIG difference! The EON’s “Egress Lighting Integrity Test” provides the industry’s most advanced life safety system test available. To satisfy NFPA-mandated periodic and annual requirements, the EON’s Intellistat TS monitor automatically initiates the testing of all life safety circuits, regardless of egress lighting design (“always on” or “normally off”). The Intellistat TS then compares power consumption during the test period with user-defined load capacity, analyzes the data, and advises if service is required.



  • When automatically performing NFPA-mandated tests, can the EON Model EL3 energize emergency lighting circuits that are normally off, or dimmed / turned off via a local control device?

  • YES! During these NFPA-mandated tests, an optional “test activated” contact may be used to activate one or more remotely installed ZoneSaver-2 emergency lighting control units. When activated, the ZoneSaver-2 will feed emergency power to egress lighting that is normally off, or dimmed / turned off via a local control device. This option allows for automatic testing of the locally controlled life safety circuit and the ZoneSaver-2 control unit. Consult factory for product and application details.



  • Is the EON Model EL3 easy to install?

  • YES! The EON’s 90 minute configuration requires only one (1) battery cabinet, and only batteries with front access terminals are used. This makes installation easy and less time consuming – installation is straightforward and DC connections are easily made!



  • Does the EON Model EL3 provide remote monitoring?

  • YES! Option one is isolated, potential free (Form C) Status / Alarm Relay Contacts, accessible via a terminal strip for a hardwired connection to building monitoring and security systems. Option two is network communications. The EON’s NetMinder™ option communicates system status, test results, alarms, and electrical measurements via BACnet/IP or BACnet MS/TP, Ethernet TCP/IP, MODBUS TCP, or MODBUS RS485.



  • Can the EON Model EL3 be provided with output branch circuit breakers?

  • YES! Provided in a side-mounted 14” wide, front access distribution cabinet, a total of 12 pole positions per phase (36 total) are available to accommodate 1, 2, and 3 pole circuit breakers fed from an inverter system output of 208/120 VAC or 248/277 VAC. These circuit breakers are located behind a secured, lockable, hinged door; and can be factory-wired to the normally on bus and/or normally off bus in any combination specified.



  • Can the EON Model EL3’s output branch breakers be monitored?

  • YES! Monitored output circuit breakers are available, reducing the number of pole positions to 8 per phase (24 total). If a circuit breaker is open, the Intellistat TS™ monitor sounds an alarm. Optional alarm relay contacts are also available.



  • Is the EON Model EL3 capable of operating both normally off and normally on lighting fixtures?

  • YES! The EON has a normally on output bus and an optional normally off output bus. Both outputs may be configured with branch circuit breakers, allowing for an easy and less expensive installation.



  • When supplying power to normally off emergency lights, are there any application issues to consider?

  • YES. Adjustable transfer on delay and transfer off delay settings are often used. The transfer off delay in particular is often set at 10 to 15 minutes, which allows plenty of time for HID fixtures (if used in the area) to regain their full illumination. These adjustable time delays are standard when the EON’s normally off bus is selected.



  • Can all inverter systems handle the high inrush current associated with energizing normally off emergency fixtures?

  • NO. Other manufacturers’ products may shut down if the high inrush current exceeds the inverter’s "on battery" overload rating. This is not the case with the EON Model EL3! The EON’s normally off bus option includes a user-programmable 0 to 3 second soft start control. This control limits the high inrush current and assures compatibility with various lighting types and manufacturers.



  • Is it important that lighting inverter systems provide a regulated output to emergency fixtures?

  • The answer is YES for many reasons. Here are some of them. A regulated voltage source: 1) Provides stable voltage to sensitive light fixtures, e.g. HID and LED fixtures. 2) Minimizes voltage drops associated with longer wire runs. 3) Results in less-frequent replacement of ballasts, LED drivers, and lamps in particular! 4) Facility egress lumens are maintained 100% (will not diminish) over the full 90 minutes of emergency power.



  • Is the EON Model EL3 a fast transfer lighting inverter system?

  • The answer is NO…its better! Fast transfer systems do experience a break in power. The EON has an online, double conversion topology, which means that the inverter is always on. If there is a loss of power, the inverter will draw energy from the batteries instead of the normal AC input source, with no break in the power. Thus, the EON exceeds the performance of all fast transfer systems.



  • Does a “fast-transfer” lighting inverter provide clean, stable power to LED fixtures when operating from the AC input power source?

  • The answer is NO. Fast-transfer inverter systems feed the AC input power source directly to the LED fixtures. The quality of the power feeding the LED fixtures depends on the quality of the AC power source. If voltage sags, surges and transients are present…the LED fixtures will be affected, often causing premature failure.



  • Does the EON Model EL3 have a transfer time, and if so, is it important?

  • The EON DOES NOT have a transfer time because of its online, double conversion topology. Transfer time is the time it takes to recognize and deliver emergency power. The transfer time of any standby or “fast transfer” inverter results in a momentary interruption or break in output voltage. For many applications, this is simply not desirable. A zero transfer time insures that there is no interruption of power to the lighting fixtures. This is a very important factor with HID and high pressure sodium lighting. Lighting control systems and alarm circuits may also need a no break type system because of the circuit power requirements.



  • Is the EON Model EL3 compatible with HID and high pressure sodium lighting?

  • YES! The EON is a true no-break lighting inverter system, 100% compatible with HID and HPS fixtures. Stand-by inverters produce up to a 1/2 cycle of power interruption, causing HID lighting to extinguish. Once this occurs, it will typically take the lamp 10 minutes or so to regain full illumination.